Sådan finder du ud af, hvad der er galt med din ovn

Sådan finder du ud af, hvad der er galt med din ovn

Hvordan en ovn fungerer, og hvordan den tænder og slukker

Ofte er den bedste måde at finde ud af, hvad der er galt med noget, at vide, hvordan det skal fungere. Hvis du kender rækkefølgen af ​​operationer, kan du finde ud af, hvor sekvensen forstyrres. Din ovn er ingen undtagelse fra reglen.

Når din ovn kaldes i aktion af termostaten, er der et rim og grund til den procedure, det følger for at tænde sig selv sikkert. Næste gang din ovn ikke reagerer på opkaldet, vil du kunne se, hvor problemet ligger, og du kan enten beslutte, at det ligger inden for dine kompetencer og ressourcer at reparere det, eller at du har brug for en professionel VVS-tekniker til at håndtere problemet for dig.

Følgende diskussion kan spare dig for tid og penge, uanset om du selv løser problemet eller ender med at vise problemet for din servicetekniker.

Skydningsordre: Trin til driften af ​​en moderne tvungen luftovn

Når termostaten beder om varme, springer ovnen i aktion gennem trinene og komponenterne nedenfor. Du kan se mange af disse komponenter i videoen.

  1. Termostaten beder ovnen om at komme på.
  2. Induktormotoren starter.
  3. Trykafbryderen bekræfter korrekt udluftning af skorstenen.
  4. Tændingsmodulet med varm overflade (hvis du har et og ikke en gnisttænding eller en pilot) begynder at lyse.
  5. Gasventilen åbnes, og gassen antændes af tændingskilden.
  6. Flammesensoren kontrollerer, at gassen er tændt.
  7. High-limit-kontakten når sin indstillede temperatur.
  8. Blæsermotoren tændes.
  9. Ovnen kører, indtil termostaten er tilfreds og beder den om at lukke ned.
  10. Gasventilen lukker.
  11. High-limit-kontakten når sin lave temperaturindstilling.
  12. Ventilatoren lukker ned.

En nyere ovn kan have endnu flere klokker og fløjter; en gammel ovn kan have lige det mindste, en gasventil og et termoelement (som en gammeldags flammesensor). Termoelementet eller flammesensoren tester, om piloten er tændt og stopper hovedgasventilen i at åbne, hvis den ikke er det. Selvfølgelig kan et ødelagt termoelement også forhindre gasventilen i at åbnes.

Termostaten

Termostaten er, hvor det hele begynder. Termostaten er egentlig bare et sæt kontakter, der åbnes og lukkes afhængigt af temperaturen, så strømmen kan strømme til bestemte kredsløb i varme- og kølesystemet. Tænk på dem som trækbroer, der svinger op og ned. De er normalt trukket op, men kan sænkes for at lukke broen og lade strømmen passere.

Når temperaturen i dit hjem falder, sænker termostaten sin bro og sender strøm til ovnen for at fortælle, at der er behov for varme. Når stuetemperaturen stiger igen, hæver termostaten sin bro og slukker for strømmen. Til klimaanlæg fungerer termostaten på samme måde, men i et spejlbillede og lukker broen, når huset bliver for varmt.

Hvis temperaturen i huset er lavere end den temperatur, som du indstiller din termostat til, fungerer din termostat muligvis ikke som den skal. Du kan teste dette ved at springe (røre sammen) de røde og hvide ledninger til din termostat. Hvis ovnen tændes, er din termostat sandsynligvis problemet.

Hvad gør ledningerne i termostaten?

Andre farver på ledninger i et hjemmesystem kan være til avancerede funktioner eller fremtidig brug.

TrådfarveHvad det styrer

Rød

Rød er til magt. Denne bærer 24 volt strøm leveret af ovnen. Denne magt venter ved "broen", indtil den får at vide, hvor den skal hen.

hvid

Hvid er til varme. Når broen (omskifteren) mellem de røde og hvide ledninger lukker, kræver termostaten varme.

Gul

Gul er til køling. Når broen (omskifteren) mellem de røde og gule ledninger lukker, kræver termostaten afkøling.

Grøn

Grøn er til fanen. Når broen mellem rød og grøn lukker, kører kun blæseren. Der kræves ingen varme eller køling.

Blå

Blå er en slyngel eller wild card. Det kan bruges til at drive en skærm eller til avancerede funktioner. Normalt pakkes det dog tilbage i væggen og bruges slet ikke.

Induktionsmotoren og blæseren

Induktormotoren og blæseren skubber udstødningen op i skorstenen og slipper af kulilte (CO). Ældre systemer var kun afhængige af "naturlig træk" for at udlufte disse gasser, men induktorer har været en god tilføjelse til ovnsystemet. De forlænger skorstenernes levetid, og når de bruges med trykafbrydere, hjælper de med at forhindre CO-forgiftning.

Quiz

Vælg det bedste svar for hvert spørgsmål. Svarnøglen er nedenfor.

  1. Hvor mange mennesker såres hvert år af CO?
    • 2,500
    • 10,000
    • 50,000
    • 100,000
  2. Hvor mange mennesker dør hvert år af CO?
    • 250
    • 750
    • 1,000
    • 1,500

Svar nøgle

  1. 10,000
  2. 1,500

Trykafbryderne

Trykafbryderens funktion er at kontrollere, at inducermotoren faktisk skubber luft op i skorstenen. Hvis skorstenen er blokeret, f.eks. Af en fuglerede, lukker trykafbryderen systemet for at eliminere risikoen for, at CO kommer ind i hjemmet. Selvfølgelig kan trykafbryderen også lukkes, hvis motoren er gammel og kører for langsomt til at tilfredsstille kontakten, eller hvis slangen fra blæseren til afbryderen er klemt eller brudt, eller selve kontakten er dårlig.

Den varme overfladetænder

Igen en ret simpel enhed i et komplekst system. Den varme overfladetænder bruger elektrisk strøm til at opvarme et meget skrøbeligt keramisk element, der ligner trækul, til en så høj temperatur, at naturgas eller propan brister i flammer, når den strømmer forbi. Den varme overflade tænding er placeret ved åbningen ved den første brænderport for at tænde gassen med det samme, når den introduceres til havnen. Dette forhindrer ophobning af uforbrændt gas i enheden.

Nogle ovne anvender det, der kaldes gnisttænding. I stedet for en rødglødende overflade skaber en gnisttænding en række gnister for at antænde gassen.

Det er ikke vigtigt, om du har varm overflade eller elektronisk tænding i din ovn; det vigtige er, at du undgår at bruge et pilotlys. Pilot lys affald gas; de forbrænder konstant gas i opvarmningssæsonen, og nogle mennesker lader dem brænde året rundt.

Vil du spare et par dollars? Sørg for at lukke piloten på din ovn, når den ikke bruges i sæsonen. Bare vær sikker på at du ved, hvordan du tænder det igen næste år, før du gør det.

Gasventilen

Gasventilen er grundlæggende en elektronisk styret gateway. Når enheden kalder på varme, og printkortet bekræfter, at de rigtige betingelser er opfyldt, sender enheden energi til ventilen, hvilket får den til at åbne og frigive gas, der skal antændes af tændingen eller piloten. Når varmecyklussen er løbet, afskæres energien til ventilen, og ventilen lukker igen og afbryder gastilførslen til brænderne.

Flammesensoren

Flammesensoren er meget enkel, men alligevel forårsager mange problemer for husejere. Dens eneste opgave er at kontrollere, at gassen er tændt ved at registrere varmen. Hvis der ikke er nogen varme, slukker den for gassen for at undgå farlig ophobning af gas i enheden. Flammesensoren er enkel at rette, når den går dårligt eller bare har brug for noget TLC.

Jeg skrev en simpel trin-for-trin guide til folk, der har brug for at rense deres ovnflammesensor. Se - mange problemer kan løses ved blot at rengøre en flammesensor.

Video: Rengøring af en flammesensor

High-Limit Switch

High-limit-kontakten tjener flere formål. For det første holder den ovnblæseren tændt, indtil den registrerer, at en indstillet temperatur er nået. Ellers ville ventilatoren tænde for tidligt og blæse kold luft ind i huset hver gang termostaten beder om varme.

For det andet fortæller det også blæseren, hvor længe den skal fortsætte med at køre, inden den slukkes, når termostaten er tilfreds. Ellers ville den varme luft, der er tilbage i kanalen og varmeveksleren, efter at ovnen er afskåret, bare gå til spilde.

Endelig vil endestopkontakten slukke for enheden, hvis varmeveksleren når en bestemt høj temperatur for at forhindre farlig overophedning.

Ovnens blæser og blæsermotor

Ah, endelig. Varme for os alle. Nu hvor alle sensorer er tilfredse, og grænsekontakten fortæller blæseren, at luften er varm nok til at sende ind i beboelsesområdet, vil den starte luftstrømmen.

Vores ovns blæser bruger typisk 120 volt og skubber alt fra 800 til 2000 kubikfod pr. Minut (cfm). De fleste blæsere kræver brug af en kondensator og har et halvtommer drev, der tilsluttes direkte til blæseren, medmindre du har en bæltdrevet motor.

Tid-Bit: I tilfælde af en funktionsfejl eller en strømafbrydelse til enheden er det almindeligt, at blæseren tænder og kører i en periode. Dette kan skyldes, at der er for meget varme, og at der kræves en nedkøling, eller at der kan opbygges "dårlige gasser", der skal spydes ud eller spredes af blæseren.

Udrulningsafbryderen

Spar tid og penge ved at kende din ovn

Jeg håber, dette hjalp dig med at forstå dit varmesystem lidt bedre. Her er nogle fejlfindingsideer, der involverer de dele, du lige har læst om, og her er et par flere dele tip.

  • I tilfælde af en funktionsfejl forsøger din ovn normalt at genstarte tre gange. Hvis det ved tredje forsøg ikke kan nå en vellykket tænding, går det i en lockout-tilstand i en bestemt tid, normalt en time. Nulstilling af strømmen (slukning og tænding) nulstiller normalt kortet og giver enheden mulighed for at vise dig, hvad der skete, hvis du gik glip af det.
  • Det lille blinkende lys i enheden er ikke en juledekoration eller lidt diskotek i din ovn. Dette lys blinker en slags Morse-kode, der kan føre dig til problemet, eller sige "Hej, alt er godt her." Se inden i og uden for din enhed. Der er sandsynligvis et kodediagram, der fortæller dig, hvad den prik, prik, bindestreg, bindestregsekvens, du ser, betyder.
  • Nogle irriterende lyde, som din ovn laver, kan være enkle og billige at dæmpe.
  • Pas på din ovn, og den vil sandsynligvis tage sig af dig. Men hvis du ikke renser enheden og skifter filter, som du skal, kan din ovn muligvis gå i stykker eller ødelægge din bank.

Spørgsmål og svar

Spørgsmål: Hvad kan være problemet, når varmelegemet slukkes og genstartes et par timer senere?

Svar: Problemet kan være mange ting. Denne "lockout", som ovnen går ind i, er standard efter 3 på hinanden følgende fejl. Desværre fortæller det mig ikke, hvad fiaskoen er.

Spørgsmål: Var en tekniker kommet ud i går aftes og skiftede nogle ting, og nu lyser varmeveksleren?

Svar: Er du sikker på, at det er varmeveksleren? Jeg tvivler snarere på, at det bliver varmt nok til at lyse uden at udløse en hi-limit switch.

Spørgsmål: Ovnen cykler og kører fint, men blæseren slukker ikke og fortsætter med at blæse kold luft. Hvad skal jeg gøre?

Svar: Det ser ud til, at termostatledningen, som regel den grønne, på en eller anden måde rører ved en anden ledning, sandsynligvis rød, og holder blæseren på fuld tid. Eller din stat er indstillet til "fan" i stedet for "auto". Dette er mine første gætter på lang afstand. Du kan teste trådteorien ved at fjerne den grønne statsledning fra kontrolkortet ved ovnen og derefter lade ovnen køre en anden cyklus og se om den slukker. Det vil i det mindste fortælle dig, om problemet er på lednings- / termostatsiden eller ovnens side. Hvis den slukker, er den på stat / trådsiden. Hvis ikke, er problemet i ovnen.

Spørgsmål: Min gasovn tændes 4 ° under den indstillede temperatur på termostaten. Er dette et termostatproblem?

Svar: Hvis det altid har været sådan, kan det bare være en gammel stat og ikke meget nøjagtig længere, så du vil muligvis udskifte den. Hvis ikke, og din stat er nyere, er den defekt, og de skal give dig en ny.

Spørgsmål: Jeg har en Payne-ovn, og inducerermotoren og ventilatoren kører konstant. Min varme vil ikke sparke, og den ledede kode angiver, at trykafbryderen ikke åbnede. Jeg har kontrolleret slangen, og der er ingen problemer der. Skal jeg prøve at udskifte min ovnens trykafbryder?

Svar: Det lyder som om kontakten måske er dårlig, så ja. Fordi det er billigt, ville jeg i det mindste prøve det, og hvis det ikke virker, så ring måske til en teknologi, men hvis det gør det, kan det spare dig for mange penge.

Spørgsmål: Min Goodman 96% 2-trinsovn starter normalt tidligt om morgenen, når termostaten først kalder på varme. Efter flere minutters opvarmning cykler ovnen af ​​som om termostatopkaldet var opfyldt. Systemet genoptager dog straks startcyklussen og fortsætter med at varme op i flere minutter, indtil termostatopkaldet virkelig er opfyldt. Ser det ud som et problem med høj grænseomskifter?

Svar: Jeg tror ikke det. Jeg tror, ​​det er din ovn, der skifter fra 1. til 2. trin. Dette er måske den normale funktion og slet ikke et problem.

Spørgsmål: Hvorfor kører min ovn kun korrekt, når trækdøren i bunden er slukket?

Svar: Mere end sandsynligt betyder det, at enheden ikke får nok returluft. Måske er kanalerne for små eller enheden for store. (Betydning at ventilatoren er for kraftig til kanalen) Måske kunne ventilatoren indstilles til en lavere hastighed, men du skal være forsigtig, den er ikke for langsom, eller du kan bytte et problem mod et andet, og du bliver nødt til at konsultere en tekniker for at fremstille jo da. Desværre er der langt for meget ved denne beslutning for mig at forklare her.

Spørgsmål: Hvad ville få blæseren til at arbejde i tilstanden, men ikke i den automatiske tilstand?

Svar: Blæseren tændes kun, hvis der er et kald til opvarmning / køling i “auto” -tilstand. Ventilator "til" -tilstand tænder blæseren i sig selv, men tillader stadig varme og afkøling at fungere som normalt. Hvis det ikke tændes i varme / kølig "auto" -tilstand, skal nogle være forkert på stat eller bord tror jeg.

Spørgsmål: Jeg har en Goodman-ovn, og den kører fint, så længe jeg holder termostaten på 80 og derover, men hvis jeg drejer den til lavere end 80, åbnes gasventilen ikke. Kan du hjælpe mig?

Svar: Det lyder som om stat kan være dit problem. Jeg kan ikke tænke på nogen anden grund, der ville ske.

Spørgsmål: Ovn sparker på. Hjemme temp når ønsket temp. Derefter slukkes brænderne, men blæseren fortsætter med at blæse. Normalt slukker blæseren efter ca. 100 sekunder, men lejlighedsvis fortsætter med at blæse, og den eneste måde at slukke for er sikringsboksen. Kan det være kontakten over brænderne eller kontakten, der er ved blæseren?

Svar: Blæseren gør det normalt kun, når der er en fejl. Hvis der ikke er foretaget nogen fejl og ingen ændringer for nylig, går det måske dårligt, og der er en kort, der får blæseren til at køre kontinuerligt. Kan ikke sige det helt sikkert, men det er det, jeg ville se på.

Spørgsmål: Hvor mange år holder endestopkontakter og termoelementer på en ovn?

Svar: Levetiden for mekaniske dele af enhver art vil variere meget på mange forskellige ting. Jeg kan kun sige, at de er beregnet til at vare længden af ​​deres garanti. Dette er, hvordan virksomheder finder ud af de fleste vilkår for deres garantier baseret på den forventede levetid. Hvis du ved, hvor lang garantien på dine dele er, har du en ret god idé om deres forventede levetid. Når det er sagt, hvis en del kontinuerligt fejler, har enten producenten en defekt, eller der er en underliggende grund til, at delen fortsat svigter, og du bliver nødt til at finde ud af det. Normalt er det sidstnævnte.

Spørgsmål: Jeg har en Goodman-ovn, der er omkring et år gammel. Det virker i et stykke tid med at blæse varm luft og forsøger at nå den temperatur, der er indstillet på termostaten. Efter et stykke tid forsøger at nå målet det afskærer. Når jeg ser på ovnen, ser jeg et rødt lys blinke fire gange. Vil udskiftning af et filter og placere det forkert i strømningsretningen forårsage dette problem?

Svar: Nej, jeg kan ikke se, at filteret er bagud og forårsager dette problem. Jeg er ikke sikker på, hvad der er, men det tror jeg ikke er.

Spørgsmål: Hvad er der galt med min ovn, når den antænder og derefter slukker?

Svar: Hvis det virkelig er hurtigt, er det måske flammesensoren.

Spørgsmål: Min ovn starter normalt ikke af sig selv. Jeg kan tænde og slukke for kontakten på siden af ​​ovnen, og så starter den og kører, men den starter sjældent ellers. Jeg udskiftede termostaten, men problemet er stadig. Induktormotoren er også ret ny. Lyset blinker ikke. Hvad kan det være?

Svar: Selvom jeg ikke har nok information her til at foreslå en beslutning, ville jeg ikke fortsætte med at gøre, hvad du laver uden at have et teknisk kig på det. Det kan potentielt være usikkert og koste dig flere penge, jo længere du venter, for ikke at nævne ulejligheden.

Spørgsmål: Er 80 grader for varme til at køre din gasovn?

Svar: Efter min mening ja. Det kan gøre det, men vil sandsynligvis koste en lille formue at gøre det.

Spørgsmål: Hvad ville være hovedårsagen til, at jeg skulle udskifte tændingen på min ovn tre gange i de sidste fire måneder?

Svar: Jeg vil gætte på, at du enten har den forkerte del eller forkert spænding, der kommer fra tavlen. Forskellige tændere kræver forskellige spændinger ... normalt 80 eller 120V, og hvis delen er rigtig, men spændingen ikke er, kan det forårsage det. Ellers hvis du rører ved overfladen på tændingen, hvor den lyser, kan det også ødelægge dine nye tændere. Olierne fra vores hud kan få HSI til at udbrænde.

Spørgsmål: Jeg får 4 blinkende lys fra min ovn, hvilket betyder en åben endestopkontakt. Det er -40c i dag, så jeg spekulerer på, er det overophedet og slukker bare fordi det har svært ved at følge med? Eller er der et faktisk problem?

Svar: Kontroller dit filter for god luftstrøm for at holde køligt. Hvis det er muligt, skal du kontrollere din AC-spole for at se, om den er tilsluttet eller ren for god luftstrøm. Disse ting er gratis. Hvis ikke, har du muligvis bare en dårlig grænseomskifter.

Spørgsmål: Mit lys blinker ni gange, og min kode antyder, at det er tændingen. Jeg har skiftet tændingen to gange og stadig ingen varme! Enhver hjælp ville blive meget værdsat?

Svar: Jeg er ked af, men disse koder er ikke de samme pr. Brand, og jeg kender dem ikke alle. Koden betyder bare, at den ikke kan antændes, ikke at tænderen er dårlig. (Du kan ikke røre tændingsdelen af ​​tændingen under installationen, ellers korteres den nye, men så hvis det var problemet, og du rørte ved den del af det, er det muligt, men hvis det lyser, skulle det ikke være Når det er sagt, er der mange grunde til, at en ovn ikke lader sig antændes, og jeg har brug for mere information om, hvad der sker indtil det tidspunkt eller køre elektriske tests for at finde frem til problemet.

Spørgsmål: Min ovn lyser og kører, men når den slukker, slukker pilotlyset altid, hvordan kan jeg ordne dette?

Svar: Det lyder som om du har brug for et termoelement.

Spørgsmål: Min udstødningsovn lugter svagt af naturgas, men intet inde. Er dette normalt?

Svar: Jeg har aldrig hørt om det eller løb ind i det og kan ikke tænke på, hvordan det ville være. Når det er sagt, hvis du virkelig gør det, ville jeg have det testet. Du vil aldrig lugte gas.

Spørgsmål: Hvad betyder det, hvis den hvide blæsermotortråd, der er fastgjort til en sort ledning, der forbinder til blæserbegrænsningskablet, rører blæserhuset, og det begynder at køre? Det er en kortslutning i motoren, hvilket betyder udskiftning, ikke? Blæseren tænder ikke på anden måde, og afbryderen fortsætter med at snuble.

Svar: Det lyder som et kort, ja.

Spørgsmål: Hvorfor slukkes pilotlyset, når min ovn starter?

Svar: Det kunne være en svag flamme, så enhver form for luftstrøm muligvis slukker den. Måske er det dog en intermitterende pilot. Jeg kender ikke til så mange opsætninger. Kan være et dårligt termoelement. Måske dårlig varmeveksler. Jeg kan virkelig ikke sige det helt sikkert uden at være der og køre nogle tests.

Spørgsmål: Hvad betyder "trykafbryder åben med forbrændingsluftinduktor aktiveret"?

Svar: Det betyder, at den elektriske forbindelse, som trykafbryderen formodes at "lukke" ikke, og at den er "åben", tillader ikke elektricitet at gå til næste trin, så enten er kontakten dårlig, eller der er noget, der forhindrer tilstrækkelig sugning til at gøre det "tæt". Kan være en dårlig inducer eller en blokeret skorsten, men det er typisk kontakten. Dette ville være den første ting, jeg ville kontrollere.

Spørgsmål: Jeg har en ruudovn, der er omkring 4 år gammel. For nylig er det begyndt at kort cyklus. Jeg har kontrolleret alt og endda skiftet filter, men det gør stadig det samme. Jeg har været i stand til at tage døren af, og den fungerer fint, men når jeg sætter døren tilbage, kortsluttes den igen. Hvad kan problemet være?

Svar: Det kan være snavset og ønsker mere luft, men det kan også bare være drastisk lave temperaturer, der får enheden til at køre mere for at holde trit. Min gør.

Spørgsmål: Jeg har en Goodman tvungen luftovn, der er omkring 13 år gammel. Jeg udskiftede trykafbryderen et par år tilbage og har fået blæseren udskiftet for omkring et år siden. Jeg har i øjeblikket problemer med at få varme. Ovnen kører, men nogle gange blæser den ikke varm luft. Når det sker, lyder det som om brænderne tændes og slukkes. Jeg har allerede udskiftet termostaten, men det fungerede ikke. Nogle ideer?

Svar: Hvis brænderne starter og næsten øjeblikkeligt tænker, ville min første tanke være flammesensoren, men ud over det kan jeg ikke rådgive på baggrund af de angivne oplysninger.

Spørgsmål: Hvorfor tænder ikke den udvendige ventilator for min ovn? Den sidder fast.

Svar: Hvis din ventilator sidder fast, har motoren sandsynligvis låst sig og skal udskiftes.

Spørgsmål: Hvilken temperatur skal luft komme ud af varmevekslingen? Er 113 grader korrekte, eller skal det være mellem 120-125 grader?

Svar: Ventilatorgrænseafbryderen skal fortælle dig, hvilket område temperaturerne skal køre i. EX- 130-160 grader kan være stemplet på det.

Spørgsmål: Mens ovnen er i en lang varmecyklus (~ 30 minutter), vil jeg høre inducermotoren afbrudt i 1 sekund, og derefter genstarter den og fortsætter med at køre. Denne 1 sekundslukning af inducereren kan ske 3 eller 4 gange i løbet af 30 minutters varmecyklus. Kun induktormotoren afbrydes i denne periode på 1 sekund. Ovnblæseren kører fortsat. Har IDM brug for udskiftning eller muligvis den runde manuelle Honeywell termostat? 14 år Tempstar-ovn.

Svar: Staten ville ikke have noget at gøre med det. Har du en induktor med variabel hastighed? Måske ændre hastigheder? Hvis ikke, skal det køre hele cyklussen, for hvis den stopper, åbnes trykafbryderen og lukker enheden, og hvis det er tilfældet for dig, skal du være glad, det er kun et sekund, ellers har du ikke varme. Det kan være en god idé at få det tjekket ud, før det haster.

Spørgsmål: Min gasovn slukker, kører et par minutter og slukker derefter. Jeg har udskiftet sikringen og har også udskiftet motoren. Hvad mere kan det være?

Svar: Jeg ville ikke erstatte ting, medmindre jeg vidste, at de var dårlige for at spare penge. Jeg kan ikke sige baseret på oplysningerne her, men at finde ud af, på hvilket tidspunkt i cyklussen det stopper, kan hjælpe. Måske ville det være bedst at teste kredsløbet, hvis du ved hvad du leder efter. Hvis ikke, skal du ringe til en teknologi og lade dem diagnosticere.

Spørgsmål: Mit koldluftindsugningsrør blæser varm luft, efter at induktorventilatorens lukning er slukket, er det normalt?

Svar: Nej. Indtaget må aldrig blæse luft ud.

Spørgsmål: Hvis en inducerblæser fungerer, men måske bliver slidt, kan det medføre, at en trykafbryder ikke fungerer korrekt?

Svar: Det kunne, ja. Det trækker ikke nok af et vakuum til at udløse kontakten.

Spørgsmål: Min 1979 Rheem-ovn i mit ovenpå varmelegeme fungerer godt med 1/2 blå 1/2 gullig pilotflamme. Inde i døren, hvor den ligger, er meget varm at røre ved, og også indersiden af ​​skabet opvarmes! Jeg er bange for at bruge min varmelegeme, kan det være en brandfare? Hvad kan forårsage den varme dør og varmen inde i skabet? Hvad skal kontrolleres?

Svar: Jeg tænker, at det er varmt sådan, fordi det sandsynligvis er en naturlig træk enhed og er i et begrænset rum. Når jeg ser, at det er næsten 40 år, kan jeg overveje at budgettere til en erstatning og helt sikkert investere i en røg / CO-detektor.

Spørgsmål: Jeg installerede min nye Patriot 80 olieovn. Fyrede det op, og alt fungerede! Brænderen startede, løb for sin cyklus og lukkede ned. Men så bemærkede jeg, at blæseren til bevægende varme ikke startede. Hvad skal jeg kontrollere?

Svar: Da enheden er ny, vil jeg først kontrollere for en løs forbindelse. Derfra skal du bare teste kredsløbene og se, hvor sammenbruddet er, og derefter bestemme hvorfor. Der er et par for mange muligheder for at liste op baseret på de angivne oplysninger.

Spørgsmål: Hej. Jeg har en to år gammel RUUD-gasovn. Det kører i nøjagtigt 8 minutter, så slukker alt og genstarter efter 30 sekunder. Denne cyklus gentages, indtil den ønskede temperatur er nået. Jeg gik forbi termostaten, og det samme sker. Nogen forslag?

Svar: Nogle gange vil en 2-trinsovn gøre det mellem trin, men hvis det konsekvent sker i hele cyklussen, og du har sprunget over stat, ville jeg først have mistanke om hejgrænsen. Kontroller dit filter, og hvis du ikke har fået enheden renset ... kan det være, at der ikke kommer for meget luft ud af plenumet. Dette er bare et gæt langt væk, og hvad jeg ville tjekke næste, hvis jeg var der.

Spørgsmål: Min ovn giver mig en fejl, der siger "tjek tænding eller jord." Alt fungerer korrekt, indtil blæseren sparker i gang. På det tidspunkt slukkes brænderne, og blæseren kører i ca. et minut. Derefter slukker det, og processen starter forfra. Er det noget, jeg kan tage fat på?

Svar: Desværre, selvom det kan være noget simpelt, som du muligvis kan løse, kan jeg ikke hjælpe med at finde frem til problemet uden at køre tests. Prøv at nulstille afbryderen og kontrollere dit filter. Se om der sker noget, der ser ud til almindeligt, men ellers skal der sandsynligvis køres elektriske tests. Undskyld.

Spørgsmål: HVORFOR udløser den elektriske ovn afbryderen, men ikke AC?

Svar: Disse to enheder er på separate kredsløb (eller burde være), så det er ikke unormalt.

Spørgsmål: Skal den udvendige ventilator til HVAC-enhed køre, når du bruger varmelegemet?

Svar: Det ville være en varmepumpe og ikke altid. Ventilatoren køler kompressoren ... ikke et problem for de fleste lige nu, så den kører ikke, hvis den ikke er nødvendig.

Spørgsmål: Min ovn er 10 år gammel og rengøres og kontrolleres af det samme firma to gange om året. For en måned siden kom en fyr ud og rensede den som ingen andre nogensinde har gjort. Han havde stykker overalt! Nu er filtrene beskidte hver anden uge ... nogen idé hvorfor? Sortlig farve.

Svar: Hvis blæseren ikke var taget ud og renset før, kunne den fungere bedre og trække mere støv ind.

Spørgsmål: Hvordan fikser jeg en ovn, når der banker, når den er tændt, og når den er slukket?

Svar: Hvis det er oliepåfyldning af kanalens arbejde (som normalt er den slags lyd ... under tryk og trykaflastning med blæseren) skal du lokalisere det svage punkt og forstærke det.

Spørgsmål: hvorfor blæser kører hele tiden og slukker aldrig?

Svar: Hvis det kører "hele tiden", er enten din blæserafbryder indstillet til "blæser" i stedet for "auto", eller der er en kortslutning i enten lavspændingsledningerne, stat eller på tavlen. Du kan afbryde lavspændingen fra kortet for at se, om den stopper. Det vil fortælle dig, om problemet er tavlen (hvis det fortsætter med at køre), eller om det er i ledningerne og stat. Tilslut derefter ledningerne der igen og frakobl statussen. Hvis ventilatoren fortsætter med at køre, er statistikken i orden, og problemet er ledningen. Grøn ledning styrer blæseren. Så rød berøring af grønt ville få blæseren til at køre kontinuerligt. Prøv kun dette, hvis du er sikker på at du ved hvad du laver.

Spørgsmål: Jeg installerer en ny trækinduktor (udstødningsblæser), der fulgte med fire endestopkontakter, der har fire forskellige farvede prikker (hvid, gul, rød & blå) på dem. Jeg har kun to endestopkontakter på min ovn, den øverste endestopkontakt er blå prikket og den nederste er gul prikket. Er jeg korrekt ved at bruge den nye gule stiplede grænsekontakt, da jeg kun udskifter min nuværende gule stiplede grænsekontakt?

Svar: Det lyder som om du har et "kit", der kan bruges på forskellige enheder, så jeg vil sige ja, du skal have det fint, selvom jeg sandsynligvis ville gøre begge grænser, men i det mindste beholde dem, der går med din enhed, som reservedele.

Spørgsmål: Min ovn fungerer fint. Det udluftes foran huset. Hvorfor har den kun sådan en mærkelig lugt udenfor, når ovnen tændes?

Svar: De eneste dårlige lugte (rådne æglignende), som jeg er opmærksom på, har været et resultat af en dårlig varmeveksler. Jeg siger ikke med sikkerhed, at det er dig, fordi jeg ikke ved, hvad du lugter, men der er normalt ingen dårlig lugt fra disse ventilationskanaler.

Spørgsmål: Induktormotoren starter ikke eller drejer et halvt omdrejningstal, når der startes et kald til varme fra termostaten. Motoren drejer ret godt, når den drejes i hånden. Er min ovns induktormotor brudt, eller fungerer der ikke noget andet, som f.eks. Trykafbryderen? Lyset giver mig en kode 31.

Svar: Du har muligvis en kondensator på din inducer, der er dårlig. Ikke alle enheder har disse, men nogle har. Hvis ikke så sender bestyrelsen måske ikke strøm til induceren. Du bliver nødt til at kontrollere spændingen for at sikre, at det sker, og hvis det er, er motoren måske stadig dårlig, selvom den drejer frit.

Spørgsmål: Ovnen kører og varmer huset fint, men huset er tørt. Ovnens luftfugter fungerer, men huset er stadig tørt? Hvad kan jeg prøve?

Svar: Har du skruet op for luftfugtighedsprocenten skabt af luftfugteren? Tilføjelse af fugtighed er den eneste måde at løse problemet på. Måske er din luftfugter ikke dimensioneret korrekt. Jeg ville ønske, at jeg kunne tilføje noget mere, men der er virkelig ingen "rettelse", hvis alt fungerer.

Spørgsmål: Næsten hver morgen, når vi vågner op, og vores hus fryser. Når jeg går til vores ovn, ser jeg fejlkoder 10 og 61. Hvorfor har vi konsekvent en blæserfejl? Ovnen er helt ny!

Svar: Selvom jeg ikke kan være sikker på, at dette er dit problem, ofte når nogen har ensartede blæserproblemer, er det fordi luften, der kommer til ovnen, er utilstrækkelig. Det kan være et snavset filter, underdimensioneret kanal eller ikke nok returluftsregistre. Dette er især almindeligt, når du installerer en ny enhed på ældre kanaler til hjemmet, og kanalen er ikke blevet foretaget korrekt.

Spørgsmål: Min gasovn model nugm100ehb1 tager forbrændingsluft inde fra hjemmet, er dette korrekt eller korrekt?

Svar: Ja, så længe der er nok ledig plads. Der er et diagram i installationsmanualen, der fortæller dig, hvor mange kvadratmeter du skal have. Jeg er heller ikke sikker på, om det gælder for din model, men nogle siger, at det vil forkorte garantien på enheden. Det kan være en god idé at se i din manual og garantioplysninger for at finde ud af det.

Spørgsmål: Vores ovn fungerer kun, når vi løsner luftindtagsrøret fra dets forbindelse til ovnen. Vi har sørget for, at luftindtagsrøret er klart. Ovnen er en halvfems procent effektiv ovn. Nogen forslag?

Svar: Det er muligt, at luftindtaget er for lille til den afstand, det kører. Du bliver nødt til at se installationsvejledningen for at se, hvad den rigtige størrelse baseret på afstand anbefales.

Spørgsmål: Hvorfor åbner min ovngasventil hele tiden?

Svar: Jeg vil vove at sige, om det enten er defekt og skal udskiftes, eller at det er forbundet forkert og modtager konstant strøm i stedet for at åbne på kommando.

Spørgsmål: Min termostat har en timer (forlade / returnere osv.), Så min ovn kommer op på temperatur første gang den bliver bedt om det, men lukker derefter indtil næste interval. Hvad tror du det er?

Svar: Der er hundredvis af termostater på markedet, så jeg kan ikke fortælle dig meget ud over at læse din manual og dobbelttjekke din programmering. Det lyder som om noget måske er blevet programmeret forkert. Desværre programmerer de alle forskelligt, så jeg vil ikke gætte.

© 2012 Dan Reed

Suzie N den 13. marts 2020:

Jeg har en 6-årig Goodman-propanovn, og for nylig har ovninduktoren været nødt til at blæse luft 4 til 5 gange inden varmen sparker på. En servicemand kom ud og rensede alt, og det fungerede naturligvis perfekt, mens han var her; det startede dog blæserlydene igen senere. Han mener, det er inducereren, men jeg troede, at blæserinducerens opgave var at blæse luft. Har du nogen ideer

Merlin M den 6. oktober 2019:

Hej Dan,

Fantastisk artikel, tak.

Vi har en gammel Heil-ovn, der snart skal udskiftes. Indtil da prøver vi at halte forbi (lille by og entreprenører har meget travlt)

Vores ovn kommer mellem trin 7 og 8, men de korte cyklusser. After the system warms up (flame burns for ~60 sec) the blower comes on but then the system starts to short cycle. Flame is on for about 2sec then off, one 2sec off and so on. Heat is delivered to the vents but clearly this is not right.

I have done the basic, check filter, change thermostat batteries, looks on roof to ensure eventing. At first I thought flame sensor but tow problems with that,

One, if that was the issue why would the furnace warm up. My thought is a bad sensor would prevent this. And two, for the life of me I cannot see a flame sensor on this unit.

Any suggestions?

Camster den 13. marts 2019:

Hej Dan. So yesterday a furnace technician came to inspect my 23 year old Lennox High Efficiency Gas furnace. He said that the temperature in one of the ducts registered 68 degrees and if it reaches 70 the furnace will shut down. He said I probably need a new furnace. What is he talking about please?

[email protected] on March 08, 2019:

Every time we cut our furnace on into the old one it's one of the fan blowers fucking ancient and now it smells and it's smoking so when we cut it off and then we try to cut it back on the next day it just doesn't even turn on what could it be it was really dusty and stuff my life but another filter for it and it's just not working we cut the switches back on through the fuse box and it doesn't cut on and it's getting cold man what do I do what could it be

connie on January 01, 2019:

I have a new York furnace in my garage. I noticed that I feel warm air coming out of the furnace box in garage, while it is dispenseing warm air into the living space.

Dan Reed (author) on November 21, 2018:

Joe689 - So here's a theory. The old stat was perhaps inaccurate thus maybe the furnace wasn't heating up as much. No perhaps it's running longer thus increasing the temperature in the duct. As it heats up, the duct may expand and as the heat shuts off but the fan is still running and the temperature dropping the duct contracts and causes a "thump" or oil canning sound. I can't really see any other way a thermostat could cause this to start happening other than pure coincidence.

Joe689 on November 19, 2018:

Hi Dan, thank you for the detailed run down. Very easy to follow and intuitive. Thanks for making a complex subject a little easier.

I have a Luxaire gas furnace. I just installed a new thermostat, and started to observe some different behavior. When the thermostat reaches its temp, I hear the "clicks", and then right after the furnace make a thump, deep enough to hear through the floor, and then one more thump almost right after. The fans continues to run for a minute, and turns off. This did not happen with old thermostat. The "thumps" also does not happen all the time. I try to recreate it by toggle the temp up and down but can not get it to repeat. Only when it has been on for some time, does this thump upon signal to turn off occur. And it does not happen all the time. By the way, this is for heat. What could this be? I know it is not the fan because the fan does not turn off right away. It is right might the thermostat clicks.

It never happened with old thermostat. I am about 99% sure I wired it correctly. All my wires were labeled, and I also wrote down what lettered slots they were going in on the former thermostat. With that, it was pretty much 1:1 with the new thermostat.

Tak på forhånd

Dan Reed (author) on November 15, 2018:

Ray - While I can't be sure what the issue you're having is I can say that typically a unit that runs until there is a failure will automatically kick on the blower as a default safety feature but it should shut off within 5 minutes or so after that. If you're having a limit issue, this could be why you're having problems. Perhaps, since the part is cheap and easy to change, try replacing it and see if that doesn't resolve the issue.

Ray Brewer on November 15, 2018:

I have a furnace that if it stays on for a long period of time will trip the limit switch and blow cold air and the only way to shut it off is switch the breaker off. I have a new filter and all my vents are open. Not sure what else to check?

Dan Reed (author) on October 29, 2018:

Ryan - There are a few things that could be going on and it would probably be best to get an HVAC technician out there to look at it. Gas isn't anything to mess with and hopefully not but you could have a heat exchanger issue and that would definitely require a tech to repair. Good news would be that you likely still have a warranty on the exchanger if it is your problem. (Not the labor to install it but the part itself.)

Casey Rohman on October 28, 2018:

Thank you very much for your reply, Mr. Robbins. My post here didn't appear when I checked back after posting, thus my late response. The breaker is the proper size, and no other electrical problems are appearing in the house.

However, your advice regarding an electrical problem was correct. I think that even though I was careful to reconnect the new control panel properly, it seems likely that at least one of the connections was a bit loose. After I went through and rechecked them all as well as other electrical connections in the furnace, the problem disappeared and the furnace has been functioning properly since. Your patience and willingness to help are much appreciated!

Ryan Jewell on October 26, 2018:

I have aTrane 2 stage furnace. It makes it to around item 7 in your start up list. The furnace will be lit for about 15-20 seconds and then go out... I can hear a waffling whistle noise and see fluttering in the flame at the exit of the gas tubes like it has too much air or not enough gas flowing. And then the middle to further away from ignitor gas lines blow out and it cuts gas to the unit to shut off. Any thoughts on what wrong?

Dan Reed (author) on October 26, 2018:

You're welcome Brian. Glad I could help some. Best wishes!

Dan Reed (author) on October 26, 2018:

Tom - I'm sorry no. There isn't enough here for me to offer sound advice. Perhaps the limit? Those are a common failure in older furnaces.

Brian S. Pollack on October 25, 2018:

Hi Dan,

Thanks for the input. It is the pressure switch. I can now return the control panel I ordered and had someone else install the pressure switch. Next time i'll know. thanks for your expertise!

Tom on October 25, 2018:

I have a old furnace it’s cal a Stewart Warner . It about 40 years old. I just had the thermal coupling replace and it was working fine then it warm up outside so I turn it off. Then when I needed heat again it wouldn’t come on. I can hear the click in the thermostat To on the furnace but nothing any idea?

Dan Reed (author) 23. oktober 2018:

Don - This sounds more like a pressure switch problem to me. Perhaps check out my article on that and see if it helps.

Dan Reed (author) 23. oktober 2018:

Brian - I would be more inclined to think it's the flame sensor or pressure switch. If the sensor is dirty or pressure switch is weak, it could be giving a false failure that can happen within split seconds causing the valve to click open and closed but so fast that the flames don't actually go out. This is my thought from a far. Perhaps check them and see.

Dan Reed (author) 23. oktober 2018:

Casey - When there are multiple part failures in a row like this I always consider the incoming power and circuit. Is the breaker sized properly? Is the furnace on it's own dedicated breaker? Are there any other "occurrences" in the home with other appliances or lights? I wish I had an easy answer here but testing will definitely be required to definitively pinpoint the issue.

don murray on October 20, 2018:

Hi Dan, I have an older carrier furnace, light is on constantly, and no blinking noticed. Inducer spins, I hear the blower sound, igniter glows hot, then everything shuts down.

I just replaced the gas valve, and now the same thing is happening. Any ideas? could the gas valve I just put in be bad ? The gas is turned on to the furnace, lol...

Brian Pollack on October 20, 2018:

I am trying to figure out what going on with my Trane XE80. It can be either the limit switch, control panel, or gas valve that is clicking. The furnace runs, no problems with the start. It remains on and about ten minutes into blowing hot air it will click about 5-10x. The flames will flicker on and off with each click. The furnace is still running, the flames come back continually and the clicking goes away.

I have already checked the thermistor. Any thoughts?

Dan Reed (author) on October 18, 2018:

While your message isn't clear to me I can say that changing the filter will help keep temps down but has nothing to do with the pressure switch. The problem may be the pressure switch however the 2 are not related. Perhaps check out this article and see if it helps...https://dengarden.com/appliances/Everything-You-Ne...

Reed Wickstrom on October 17, 2018:

I have a Heil 2 stage filter and it does nothing when thermostat calls for heat; however, if I unplug the limit switch the inducer motor starts and then shuts off around 30 seconds later after I reconnect it. FYI, I checked the furnace filter and it was dirty. I am thinking that it overheated. Do you have any suggestions.

Dan Reed (author) on October 11, 2018:

Call the company who installed it and ask them to check it out.

Carol miller on October 11, 2018:

I have a 2 month old heater/air con. Installed and it gets very very hot to touch. What should i do?

Dan Reed (author) on May 16, 2018:

Craigh S - I can't be sure without testing. Maybe the board is bad? Are you sure it's the rollout switch and not the temperature sensor on the blower housing?

Craigh S on May 14, 2018:

Why would rollout switch error show when it a/c is used but not when heat is used?

Dan Reed (author) on May 01, 2018:

Derek - I really can't think off why these two would be running simultaneously because of your cutting concrete unless you got water on the board and shorted something out. I could maybe understand just the blower but not along with the inducer. And are you sure this is a result of your work or that you just happened to notice because you spent so much time down there?

dgrandstaff on May 01, 2018:

I was cutting concrete close to the furnace and there was a lot of dust, now the exhaust fan and the blower run at the same time nonstop.

Dee Kae on March 25, 2018:

Tak fordi du svarede.

Dan Reed (author) on March 25, 2018:

Well Dee, Like other mechanical working things, they sometimes just do something weird and turning off and on the stat can trigger a new call and voila, it works. I wish I could offer a better explanation but it does happen. My furnace will sometimes shutdown on a real cold night because I believe the "heavy" cold air along with a right wind direction overcomes the pressure switch/inducer and can trigger a lock out. Wind stops, I reset the unit, voila...it works. It is very difficult when a cause can't be pinpointed. Next time the furnace shuts down see if you can catch the blinking red light code and maybe that would help.

Dee Kae on March 25, 2018:

I have a Tud-B series older Trane furnace. It is cleaned professionally every fall and last fall HVAC said it's still in great condition. On Feb. 22, March 3, March 6 and March 25, the furnace stopped working but started again when the thermostat was turned off and back on. I haven't called HVAC yet because it's happened late at night and on weekends so it has seemed to be better to try turning it off and on first. Once last summer the newer air conditioner stopped and they couldn't duplicate the problem because it started working when they got here and turned the thermostat back on. I have a newer electronic programmable thermostat. I've changed the batteries twice (display was still working), cleaned it (no visible dust) and tightened a loose anchor screw. What else could cause my problem besides a faulty thermostat? Turning the thermostat off and right back on has turned the furnace back on all four times. Tak skal du have!

Dan Reed (author) on March 06, 2018:

I would say perhaps you have a slow close gas valve however if it keeps running or goes into lock out then I don't think that's it. It sounds like the valve itself maybe going bad. It's a "normally closed" valve and if the power is being lost in the valve then it will not hold it open and thus creating this intermittent issue. I can't swear to it without running tests but I would have it checked out because it will cause other components to wear out if it's constantly starting and stopping.

RandysPCs on March 06, 2018:

I have a Coleman furnace that acts like it's running out of gas sometimes. I have watched it and what happens is, the induction fan runs, ignitor glows, gas lights but then gradually the flame gets smaller and goes out. Then the gas valve clicks off and the cycle starts over, sometimes it will stay running sometimes it goes into lock out. Any ideas?

Dan Reed (author) on March 06, 2018:

Lowski - I'm nearly positive it's the flame sensor and is probably just a bit in need of a cleaning. You likely won't even be able to see dirt on it but it doesn't take much at all. I've written on how to do this so perhaps if you need some guidance you could check that out. Thanks for reading.

lowski on March 05, 2018:

Hi Dan,

I recently replaced the circuit board on my Ruud 80%. Apparently there was a bad relay, causing my inducer motor to constantly switch between hi and low, delaying the furnace from ever igniting. Since I switched out the board, it has worked fine, with the caveat that every once in awhile, when the inducer motor turns on and the pressure switch makes, I hear the gas ignite but then turn off right away; but the blower motor still comes on and blows cold air. Once the blower motor turns off, the inducer comes immediately on and the whole sequence starts again, but this time with the flame staying lit and working properly. Thoughts?

Dan Reed (author) on February 26, 2018:

Roger, There are a lot of possibilities based on the info you've provided. I would need more to offer any sound advice. Maybe igniter is bad? Maybe inducer/pressure switch is preventing it due to obstruction or part failure? Maybe board? I'm sorry but I can't help much at this time.

Roger on February 26, 2018:

furnace turns on but the igniters don't light up.

Dan Reed (author) on January 27, 2018:

I don't think it's either to be honest. Sounds more like an intermittent pressure switch issue. See my reply to John.

Dan Reed (author) on January 27, 2018:

Sounds similar to how a pressure switch will act sometimes. It's cheap and easy to fix so maybe give it a try if it's in the budget.

Jakobsdad on January 26, 2018:

My furnace works perfectly for one or two cycles then it goes through the start up process but the igniter doesn't come on. The furnace continues through the whole start up process then blows regular air through the system. if I turn the thermostat to the off position and then back to heat it works perfectly for one or two cycles then repeats. do you think this is a thermostat issue or an igniter issue? the igniter works as it should after the manual power cycle from the thermostat.

John on January 26, 2018:

My furnace works perfectly for one or two cycles then when the thermostat calls for heat the igniter doesn't light and it blows cold air only. I can turn the unit off then right back on and it works perfectly again until one or two more cycles then I have to repeat a powering down to get it to work

Kathleen8 on January 26, 2018:

Du har sandsynligvis ret! hahahhaha I figure it there was a problem, it would have shown itself by now. Tak!

Dan Reed (author) on January 25, 2018:

And though I hate to say it, that may be exactly why this is an issue for you. Furnaces aren't as quite when you have to sleep next to one as they are in a basement and is likely why the evenings seem worse...it's quieter, colder, and you're right there for it all.

Kathleen8 on January 25, 2018:

Honestly, I don't know about furnaces. It's a Carrier 59SC5A I believe.. I don't believe the manual says it's 2 stage. I thought the filter was dirty, so I changed it with a nice Filtrete filter and no sluggish noises upon the start of cycling. Then 3 weeks later, it started doing it again. I looked at the filter and it was dirty again. So, I jut put in a filter from ACE Hardware and the noise came back. It will only usually happen in the evening when it actually does happen.. You hear the switch and then it's this sluggish noise like it's having a bit of trouble getting going) from what I assume is the air draft inducer and then it starts blowing just fine. My brother thinks maybe it's just working harder? I can't believe I'm the only person with this issue..then again, I live in a tiny house and the furnace is right there next to my bedroom so I hear EVERYTHING.

Dan Reed (author) on January 25, 2018:

Kathleen8 - I can't really say much based on the information here but since it's condensing...is there a chance it's also a 2 stage unit??? If so, the gas output and blower speeds may vary by cycle and whether it's calling for the first or second stage.

Kathleen8 on January 25, 2018:

Hi, I have a Carrier Condensing gas furnace. Sometimes, when the furnace kicks on and starts it's cycle, it sounds sluggish before the blowing begins. Most times, you hear the click, the cycling starts and it starts blowing but it seems like since we are in the midst of winter and it's on all the time, it happens for a few cycles during the evening, but not all the time... Any ideas? Could there be dust stuck somewhere? Tak!

Dan Reed (author) den 16. januar 2018:

Unfortunately there are a too many possibilities for me to say anything certain. Maybe a fan limit? Intermittent pressure switch? Gas valve? Circuit board? Unless you just want to start throwing parts at it, you'd need a tech to troubleshoot the circuit.

Phyrfitr den 16. januar 2018:

i have a york 90+ 100,000 btu single stage unit, the thermostat will call , the inducer motor will spin up the solid igniter will glow the gas valve will open and the furnace will cycle, for five minutes or so then the flame will go out but the inducer and blower motor will continue to run, the igniter will glow and the gas valve will start clicking constantly and the flame will ignite multiple times causing multiple fuel ignitions sometimes making a Poof sound, I sit and watch it thru the peep hole, this has been going on now for about A week, Any thoughts ?

Bill Fish on January 14, 2018:

Thanks for responding to my question. You said that my problem might be related to the flame sensor, with the limited info I gave ya. So I cleaned the flame sensor, which was very simple, and my furnace is working great again. I probably saved a couple hundred dollars by doing that myself. Tak igen.

Steve Stark on January 08, 2018:

I have a 14 yo Tempstar gas furnace. During a long heating cycle, the inducer motor will cut off for a second and then come back on. This happens maybe 3 or 4 times during the heating cycle. Does the IDM need replacement? Or, could the thermostat be faulty? (round manual Honeywell thermostat) Thanks

Dale den 3. januar 2018:

Have a 10 year old furnace, have it cleaned and checked twice a year. A month ago the fella took the thing apart like never before, put it back together and left. Now the filter is filthy after two weeks. That never happened before. Have any ideas what happened? Tak skal du have. 1/3/18. [email protected]

Earl den 3. januar 2018:

My furnace will not stay running unless the door is off, why?

Dan Reed (author) on December 30, 2017:

Angelo - It seems maybe the thermostat is the issue since the furnace will only turn on when the stat says to so perhaps it's not reading properly???

Dan Reed (author) on December 30, 2017:

Jeff - I'm sorry but there isn't enough for me to offer much. Check your filter. Could be a high limit switch??? Not sure though.

Angelo on December 29, 2017:

I have Lennox Meritt series that's 13 years old. It started to act weird yesterday. It will only turn the furnace on and maintain the house temperature if the thermostat is set at 73 and above. If I set the thermostat below 73, it will will not turn on the furnace.

Jeff on December 28, 2017:

I have a Coleman I replaced the pressure switch and the thermostat it is running a cycle at two set to 70 but any higher it will run as well then shut off and not fire in less I turn it back down to 70 and cut power and reset it

Dan Reed (author) den 26. december 2017:

RK - It sounds like you either need a new motor and/or motor capacitor. I don't recommend using your hand. I suppose it may be getting bad voltage from the board as another possibility but you may want to call a tech.

RK den 26. december 2017:

Hello, I have Carrier weathermaker 8000 gas furnance. Very often furnace would not start and I have to rotate the motor by hand and press the cover switch to start again.. If i leave it, it may start randomly after few hours on its own Any suggestions

Dan Reed (author) on December 17, 2017:

Craig, Though I can't say for sure from here, I would first check the hi limit and is the coil for your a/c new too? If not, perhaps it is clogged and blocking air flow??? Is the new furnace fan perhaps more powerful? If so, your ducts may not be big enough on the return side...especially if you added an air cleaner. These are my suspects. Thanks for reading.

Craig on December 15, 2017:

Have a Goodman furnace installed on 2016. I set the thermostat to 72 the furnace starts up. Runs for a while tries to make temperature but then cuts off and there is red light blinking 4 times. After a while when the temperature has dropped it kicks back in. I replaced the filter. The thermostat was recently replaced. I have checked the airflow outlet and inlet they don't have any objects. Would a leaking window sill or older windows result in this kind of behavior where the furnace cuts off? This is again a brand new furnace.

Dan Reed (author) on December 14, 2017:

Greg, I'm not sure what advice to offer based on this info. You experienced some sort of failure that is apparently intermittent so when you reset the breaker it started over and apparently didn't have the same problem at that time. In short, something is happening to shut down the unit and you'd need to know at what point in the cycle the unit shut down and caused the unit to "lockout". Any failure that happens 3 times will put the furnace into "lockout" for a set period of time before it tries again. Sorry I can't be of much help based on this info.

Greg Staples on December 13, 2017:

Furnace stopped working the other day, wiggled wires, tripped breaker back and forth, after a bit it came on and worked through the night fine. Same thing happened again the next night. Replaced the breaker because there didn't seem to be any power going to the furnace. Furnace is working so far today but when it is running it seems to ossolate power now and then. Any ideas?

Dan Reed (author) on December 11, 2017:

Thomas - It sounds like you're not getting enough air flow when the filter is in. Perhaps it's restricting the airflow just enough to make the unit overheat and shut down prior to satisfying the thermostat. Often when adding a high end air cleaner, the ducts coming to it need increased in size to allow for more air to keep the unit temperature within it's confines and not overheat the motor or exchanger. Hope this helps at least to understand what the issue MIGHT be. Thanks for reading.

Thomas on December 10, 2017:

If I remove the air filter on my electric furnace then I heat until it reaches the Nest thermostat selected target temperature. If I place the air filter in, it doesn’t reach the selected temperature but is about 4 degrees colder. What is wrong and what is the fix?

Dan Reed (author) on December 08, 2017:

Dave - They can vary. The best way to know your range is to check the High Limit/Fan Switch. There is usually a temp range on there for your unit.

Dave on December 05, 2017:

What should the heated air coming out of heat exchange Be is there a minimum temp ??? Like 120 deg ?

Dan Reed (author) on November 12, 2017:

John - That's an odd one but likely an issue with communication between the stat and furnace. I'm sorry but can't offer much there other than rechecking your programming and running electrical tests to see what's making the unit shut down in that first cycle.

John Beattie on November 11, 2017:

My gas furnace comes on for the 1st program cycle of the morning but doesn't complete the cycle and will stop with out reaching the programed setting. If I turn the furnace on/off it then acts like it completes a heat cycle without the burners on. Then in a minute or so later the furnace comes on and then regularly runs the rest of the day. what might be wrong?

Dan Reed (author) on November 10, 2017:

Ozzie - A high efficient furnace has an intake and exhaust pipe and connection usually. Sometimes guys will let the unit pull air from in the home on the intake and not run it all the way outside. In order to do that, they are supposed to make sure there is enough free square footage to provide the needed intake. Taking that door off may be giving you just enough to do the job but you shouldn't have to leave any covers off your unit to make it run. Hope that helps.

OzzieSch on November 10, 2017:

What exactly brings in the outside air for an efficient furnace? I don't get enough outside air to combust the gas. When I take off a little side cover on the furnace to let in inside air, the furnace works properly. What is my problem?

Dan Reed (author) on November 08, 2017:

Lee - If that's the case then they may need a good cleaning. I'm a little stunned though since a flame sensor should detect that the burners aren't lit since one needs to fire to fire the next and the next. ???

Dan Reed (author) on November 06, 2017:

Marco - I'm sorry but for me to help I would have to perform electrical circuit testing to pinpoint your problem here. I would start with the thermostat. Sounds like it may be suspect.

Dan Reed (author) on November 02, 2017:

Thank you Jonas!

Jonas Porter on November 01, 2017:

This was just an awesome explanation. Tak skal du have. Tak skal du have.

Dan Reed (author) on October 21, 2017:

Kevin - There is obviously a short somewhere. Likely culprits are the transformer and/or entire board. There could be other causes but this is what I'd suspect. Thanks for reading.

Trina Bowers on October 19, 2017:

Ok i checked the fuse, i clean the heating sensor and the blower is working, glow ignitor comes on, slow flashing green light. I checked the thermostat ....the problem is i cant seem to get a flame ignited i dint know what else to do...i want to call for help to be my last resort.

Jw clink on October 19, 2017:

I replaced my ignition last year and furnace work fine.

This year it will not even get hot.

Fan works fine.

Any idea?

Kevin Zoch on October 17, 2017:

I have a Trane Furnace that I determined has a blown fuse on the control panel. When I replace the fuse and push the black switch that the metal panel touches it instantly blows again.

Aaron on October 13, 2017:

I have a Colman Evcon. It is flashing 4 flashes meaning bad limit switch. Tested all switches and checked out. Have a green flash when unit not heating. Bad board?

Dan Reed (author) on October 07, 2017:

Duane - It sounds like it. If the inducer fan/motor is shot then nothing will work as it's the first step in the heating cycle and if it is bad, the whole assembly is usually sold as a piece and is typically specific to it's brand so universal parts aren't likely going to be an option for repair. You'll need to find the distributor for your brand of furnace to find the part most likely. Thanks for reading.

Duane on October 06, 2017:

The induction fan does not start it just hums. It does not spin. Is the fan bad or is there something else I should look for?

Dan Reed (author) den 11. september 2017:

Amacblue - The coil sits on top of the furnace. It's not part of the furnace. It is not always possible for a homeowner to do this since sometimes there is not way to access the underneath of the coil where dirt and such collects in which case it would need to be removed and that DEFINITELY requires a service technician. If you can however access the underside, congrats and it should be cleaned but carefully and not to bend the fins over so that air can't pass through. Thanks for reading.

Amacblue den 8. september 2017:

I would like to clean my coil on my furnace however o can't seem to locate it. It is a carrier just like the one pictured thank you

Dan Reed (author) on July 05, 2017:

Luis - You may have a blown fuse on the board. It's usually 3 amp fuse that is like that in a car. Can't say for sure but that's where I would start. Thank you for reading.

Dan Reed (author) on March 26, 2017:

Robby =- There is a laundry list of things to check from here however it doesn't seem coincidental that this is happening after the stat was changed. Sounds like perhaps your white wire isn't making good contact or in the right spot. Double check your stat wiring. Beyond that, there are too many things to check to list here. Fuse on board? Gas valve? Ignitor bad? Limt? Pressure Switch? I'm sorry I can't be more helpful from here. Thanks for reading.

robby on March 25, 2017:

My heater stopped working yesterday nigh (it had stopped once few months ago, we changed the thermostat battery and it worked fine). After it stopped working, I put a new thermostat and still no luck. These are the few observations, please help in letting me know what is wrong

1) the AC works fine with both thermostat. The AC turns on (outside the house) and the blower blows air

2)On heat, the fan ON position gets the blower working (and you can hear the blower unit below the furnace making noise).

2)On heat, auto, nothing is working. The blower does not work, the flame is not lit (however the pilot flame is lit fine)

While changing to new thermostat, twice on Heat/AUTO, the blower came on but it kept pushing cold air for minutes. Now even that is not happening. Manually pushing the switch in the furnace gets the blower going, but there is no furnace flame(only pilot flame).

Please let me know what to do next

Dan Reed (author) on March 08, 2017:

Arash - It sounds like you had/have a short circuit somewhere. If you don't have a voltmeter you will have a very hard time finding it. You may want to call a tech or you could find yourself spending a lot of money on parts you don't need or buying a part that will short again because you didn't identify the source. Thank you for reading.

Arash on March 07, 2017:

Hi Daniel, I have a Lennox hvac with two zone. My heater stopped working last month an no power on thermostats. I notice the fuse on zone controller board is blown. I changed the fuse with a 5 amp. The power return to thermostats but heater didn't turned on again. I ordere a new zone controller but again the fuse blown in new board. So I thought the problem is from main controller board. I ordered and replaced the main controller plus adaptor. Still heater doesn't work. The egniter glows but the gas valve doesn't release gas to flame. I checked the voltage on gas valve and it's not 24v. It keeps trying ignite and doesn't go to watch guard mode. Would you please help me to figure it up? tak skal du have

Ccole456 on February 21, 2017:

Tak skal du have. I looks up the difference and it appears it is an ignition board. Thanks for confirming. We have a number of things to try and hoping to keep the unit going for at least a few more months!

Dan Reed (author) on February 21, 2017:

If you have a spark ignition board then you perhaps will not have what I was thinking of. My apologies. There are so many boards out there and this was not what I was envisioning. It would be in plain site if you could change it and I don't believe you can open those without causing further damage.

Ccole456 on February 21, 2017:

Daniel- Curious if you can assist in locating the fuse on the board. The white Rogers control seems to be sealed. The fuse would be inside the case correct? The main fuse at the switch is fine we did check that one.

Dan Reed (author) on February 21, 2017:

Perhaps you've blown the fuse on the board. Typically a 3 or 5 amp automotive type fuse and/or perhaps the 120v/24v transformer took a hit. That could be the humming you hear. All of these are cheap places to start. I'm sorry but troubleshooting over the net is very tough so I try to recommend some of the simplest, cheap repairs to folks.

Ccole456 on February 20, 2017:

Daniel Robbins thanks. Nothing we have read or viewed yet has led us to the capacitor. Haven't been able to make any of the initial trouble shooting techniques give us a clear yes or no. We had a number of power failures from wind the day before it stopped working. If I understand you the the old White Rodgers control panel should illuminate to indicate at least something.

We will look into the capacitor then probably need to call technician if that doesn't work?

Dan Reed (author) on February 20, 2017:

Ccole456 - Sounds like the main blower isn't turning and that humming may be the motor trying to start. There is a capacitor usually mounted to the blower housing that may be bad and would be a cheap easy place to start and if that doesn't work, perhaps the blower is shot. That said, if the light on the board isn't lit, then you may have taken a hit electrically and then the potential possibilities get to be too many to cover here. That said, I would start at that capacitor. Thanks for reading.

Ccole456 on February 19, 2017:

York gas furnace clicks on and then you hear a low continuous buzzing noise (seems to come from near the control panel) and nothing else happens. Replaced inducer motor thinking that was the problem, same issues.

Stat working and fan doesn't turn on when switched "on" at stat. Getting power where stat wires connect to pressure switch. Tubing at pressure switch appears unblocked and in good shape.

Could it be the pressure switch? Could it be the control panel? There is one light on control panel but it doesn't illuminate, no blink code, nothing. Kan det være noget andet? Thoughts?

Jill on February 08, 2017:

Just replaced an oversized furnace with the right sized one as i was having issues with the furnance constantly coming on. I lowered the thermostat several degrees during the day so it would not come on as much. With the new furnace I thought this would all be resolved but it has not. It comes on more frequently and even with the temp set lower it comes on every 10 mins. Any advice? I've been dealing with this for 2 years and I just want an answer!

Wayne Hogan on January 31, 2017:

Have a 2-stage furnace. furnace runs great on high, runs for about 2 minutes on low then gas shuts the gas valve and the cycle repeats many times till thermostat is met. I have replaced the roll out switch and flame rod and it still occurs. Any suggestions?

Chris taft on January 22, 2017:

Carrier weathermaker has been having flame out problems, had a tech come out and tell me that the intake/exhaust wad too small and needed to be 3", so all that is changed and now it seems like it won't cycle back to back without having an issue. Turn power off to furnace and back on will work for 1 maybe 2 times. Any advice?

Dan Reed (author) on January 22, 2017:

Michael Riemer - Not real sure. Could be too large of BTU. Could be the LP kit to make it LP wasn't adjusted properly. Could be a new stat is more accurate and the old one wasn't keeping the temp as consistent. Sorry but this is a tough one that would require further investigation onsite than I can provide here.